12/24kV Full gas Insulated RMU

Short Description:

RMR is a full gas ring main unit for the secondary distribution network. RMR can be supplied in 10 different configurations suitable for most switching applications in 12/24 kV distribution networks. It complies IEC60420, GB/T11022, GB3804,GB3906 with high quality. Contact us for a low price....


Describe

Technical Tables

Drawing

General:
RMR is a ring main unit for the secondary distribution network. RMR can be supplied in 10 different configurations suitable for most switching applications in 12/24 kV distribution networks. It is extendable and combined with the SafePlus concept, which is ABB’s flexible, modular compact switchgear, they represent a complete solution for 12/24 kV secondary distribution networks. RMR and SafePlus have identical user interfaces. RMR is a completely sealed system with a stainless steel tank containing all live parts and switching functions. A sealed steel tank with constant atmospheric conditions ensures a high level of reliability as well as personnel safety and a virtually maintenance-free system. The RMR concept offers a choice of either switch-fuse combination or circuit-breaker with relay for protection of the transformer. RMR can be supplied with an integrated remote control and monitoring unit. This product is in conformity with the standards of IEC60420, GB/T11022, GB3804,GB3906


Service environment:
a) Air temperature:Maximum temperature: +40℃; Minimum temperature:-20℃
b) Humidity:Monthly average humidity 95%; Daily average humidity 90% .
c) Maximum installation altitude: 2500m
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.

 

Standard instruction:
D unit configuration
See standard configuration and features of 'Cable connecting module without earth switch module'

C unit configuration
See standard configuration and features of 'Load break switch module'
F unit configuration
See standard configuration and features of 'Load break switch and fuse combination module'
V unit configuration
See standard configuration and features of ' Vaccum switch module'

Standard combinations also includes belowing configurations:
Voltage indicator of incoming bushing capacitive character SF6 density/pressure monitor( gas meter) with each gas cell Ring for lifting Operating handle.

Note: For short circuit breaking and peak current is based on Fuse plus combination of F module.

No.
Item
Unit
C Module
V Module
Load break switch
Circuit breaker
1
Rated voltage
kV
12
24
12
24
2
Rated current
A
630
3
Rated frequency
Hz
50/60
4
1min Power frequency withstand voltage
kV
45
55
45
55
5
Lightning impulse withstand voltage
kV
75
125/150
75
125/150
6
Rated transfer current
A
1700
1400
 
7
Rated active load and close circuit breaking current
A
630
8
Rated cable charge breaking current
A
50&10
9
Rated short circuit breaking current
kA
 
20
16
10
Rated short circuit making current(peak)
kA
63
50
63
50
11
Short time (2s) withstand current, load switch/earth
kA
25/20
20/20
25/20
20/20
12
Rated withstand current (peak)
kA
63
50
63
50
13
Mechanism life
Times
3000
10000
3000
14
Dimension ( per unit)
mm
370x750x1345