Single phase pole mounted distribution transformers
Product Description:
Single phase pole mounted distribution transformers are designed and manufactured in compliance with all applicable ANSI and IEC standards. All transformers are oil filled, 65˚C rise,and designed for usual service conditions per ANSI C57.12.00. External welds are 100% coverage for added strength and corrosion withstand. Lift ears allow sling lifting while the unit is still banded to the pallet. The tank bottom weld is recessed for added protection.
| Technical Data of D9 Series Single Phase Distribution Transformer | |||||||||||||||
| Voltage Group(kV) | Loss (kW) | No-load current | Impedance | Weight (kg) | Outline Dimension (mm) | Gauge | |||||||||
| Rated Capacity | Connection Method | ||||||||||||||
| (L) | (W) | (H) | |||||||||||||
| (kVA) | HV | LV | No-load | Load | % | % | Machine | Oil | Gross | Dimension | Vertical | Horizontal | |||
| 5 | 13.8 | 0.22 0.24 | 35 | 145 | 4 | 3.5 | 50 | 40 | 130 | 530 | 450 | 850 | 400 | 250 | |
| 10 | 13.2 | 55 | 260 | 3.5 | 65 | 40 | 150 | 560 | 450 | 870 | 400 | 300 | |||
| 16 | 11 | 65 | 365 | 3.2 | 80 | 40 | 180 | 600 | 450 | 920 | 400 | 300 | |||
| 20 | 10.5 | 80 | 430 | 3 | 100 | 50 | 205 | 620 | 450 | 940 | 400 | 300 | |||
| 30 | 10 | li0 | 100 | 625 | 2.5 | 115 | 50 | 225 | 700 | 450 | 980 | 400 | 300 | ||
| 40 | li6 | 125 | 775 | 2.5 | 150 | 55 | 270 | 700 | 480 | 970 | 400 | 300 | |||
| 50 | 6.3 | 150 | 950 | 2.3 | 175 | 70 | 310 | 650 | 510 | 1100 | 400 | 300 | |||
| 63 | 6 | 180 | 1135 | 2.1 | 190 | 80 | 340 | 660 | 520 | 1100 | 400 | 300 | |||
| 80 | 200 | 1400 | 2 | 240 | 100 | 420 | 770 | 630 | 1120 | 450 | 300 | ||||
| 100 | 240 | 1650 | 1.9 | 295 | 100 | 490 | 840 | 600 | 1150 | 450 | 300 | ||||
| 125 | 285 | 1950 | 1.8 | 370 | 110 | 560 | 890 | 740 | 1160 | 500 | 400 | ||||
| 160 | 365 | 2365 | 1.7 | 430 | 130 | 650 | 950 | 790 | 1170 | 500 | 400 | ||||
Remarks: Normal Type No protection accessories.
CP Type with HV Load switch, HV fuse and LV over-current CB
SP Type: With HV load switch, HV fuse and surge arrestor
CSP Type: With HV load switch, HV fuse, surge arrestor and LV over-current CB

1. Altitude: <1000m indoor
2. Max .ambient: temperature +40℃
3.Max. daily: average temperature +30℃
4.Max .annual: average temperature +20℃
5.Min. temperature -5℃
6.Supply transformer operate under special conditions according to customer requirements.